Phoenix Contact surge protection – Lightning protection concepts for PV systems
The PV SET 1000DC is equipped with plug-in SunClix connectors and ideally suited for lightning and surge protection of individual PV strings.
Phoenix Contact surge protection – Lightning protection concepts for PV systems
The PV SET 1000DC/AC can provide protection against surges in PV strings and AC outputs of single-phase inverters.

Information

The German version is binding. The content is subject to change without prior notice.

Phoenix Contact surge protection – Lightning protection concepts for PV systems

Surge protection devices
Surges, caused by lightning strikes or switching actions, are frequently the cause of damages and failures in electrical equipment. Inverter failures mean cost-intensive equipment damages. Yield losses and repair costs are consequences, which can be prevented by surge protection devices.
Protection circuit devices
Surge protection devices must be considered for all circuits: On the DC side between L+, L- and the earth potential, and on the AC side between the phases L1, L2, L3, the neutral wire and the earth potential. In addition, all other circuits (e.g. data and measuring technology circuits), which are connected to the inverter, must be protected with suitable products.
Direct and indirect lightning protection
Direct (exterior) lightning protection must be implemented by observing the protection zones and galvanic separations by means of lightning rods for the PV generator. For indirect (interior) lightning protection, several Phoenix Contact products are available, which should be installed directly before the devices to be protected (or at the lightning protection zone transitions).
Features of the PV SETS
  • Surge protection for the DC side
  • Optional: Surge protection for the AC side
  • IP65 housing
  • Plug-in PV SET DC with SunClix
  • For one string as standard, optional multi-string available
  • PE pins for a minimum of 6 mm▓ connection to potential equalisation
Art. No. 1302156 1302157 1302158
Model Phoenix Contact VAL-MS 1000DC/2+V-FM Phoenix Contact PV SET 1000DC, PV string Phoenix Contact PV SET 1000DC/AC, PV string & AC
Scope of applications Grid-connected Stand-alone Grid-connected Stand-alone Grid-connected Stand-alone
Surge protection DC, 1 string DC, 1 string AC and DC, 1 string
Max. DC open circuit voltage 1000 V 1000 V 1000 V
Max. DC permanent voltage (L-PE) 1000 V 1000 V 1000 V
Rated voltage AC - - -
Max. AC permanent voltage (L-N / N-PE) - - 335 / 260 V
Max. pre-fuse AC - - 125 A
Rated current DC 80 A 30 A 80 A
Nominal lightning discharge current (8/20) s (L-N / N-PE) 15 kA 15 kA 15 kA
Max. lightning discharge current (8/20) s 30 kA 30 kA 30 kA
Lightning testing current (10/350) Ás - - -
Protection level (L-N / N-PE) < 5 kV < 5 / ‑ kV < 5 / 1.5 kV
Response time (L-N / N-PE) < 25 ns < 25 ns < 25 ns
Cable connection (rigid / flexible) 0.5 ‑ 35 mm▓ / 0.5 ‑ 25 mm▓ SunClix 0.5 ‑ 35 mm▓ / 0.5 ‑ 25 mm▓
Protection mode IP20 IP65 IP65
Dimensions (L / W / H) 65.5 mm / 52.5 mm / 90 mm 125 mm / 200.0 mm / 122 mm 254 mm / 180.0 mm / 123 mm
Weight 367 g 1217 g 1523 g
Warranty 2 years 2 years 2 years
Norms IEC protection class II, EN-Type T2 IEC protection class II, EN-Type T2 IEC protection class II, EN-Type T2

Art. No. 1302159 1302214 1302215
Model Phoenix Contact PV SET 5ST/600DC Phoenix Contact PV-SET 230AC/1P-RCBO Phoenix Contact PV-SET 600DC/32A-SC
Scope of applications Grid-connected Stand-alone Grid-connected Stand-alone Grid-connected Stand-alone
Surge protection DC, max. 5 strings AC, single-phased with RCD and LS DC, 2 strings, SunClix
Max. DC open circuit voltage 600 V - 600 V
Max. DC permanent voltage (L-PE) 600 V - 600 V
Rated voltage AC - 230 V -
Max. AC permanent voltage (L-N / N-PE) - 250 V -
Max. pre-fuse AC - - -
Rated current DC 30 A 16 A 25 A
Nominal lightning discharge current (8/20) s (L-N / N-PE) 15 kA 20 kA 10 kA
Max. lightning discharge current (8/20) s 40 kA 40 kA 40 kA
Lightning testing current (10/350) Ás - - -
Protection level (L-N / N-PE) < 3.6 kV < 1.5 kV < 3.1 kV
Response time (L-N / N-PE) < 25 ns < 25 / < 100 ns < 25 ns
Cable connection (rigid / flexible) 0.5 ‑ 35 mm▓ / 0.5 ‑ 25 mm▓ 2.5 ‑ 35 mm▓ / 2.5 ‑ 35 mm▓ 2.5 ‑ 6 mm▓ / 2.5 ‑ 6 mm▓
Protection mode IP65 IP65 IP65
Dimensions (L / W / H) 300 mm / 300.0 mm / 142 mm 122 mm / 200.0 mm / 125 mm 122 mm / 200.0 mm / 200 mm
Weight 3410 g 1100 g 1700 g
Warranty 2 years 2 years 2 years
Norms IEC protection class II, EN-Type T2 IEC protection class II, EN-Type T2 IEC protection class II, EN-Type T2

Art. No. 1302216 1302160 1302161
Model Phoenix Contact PV-SET 1000DC/13A-SC Phoenix Contact FLT-CP-PLUS-3S-350, AC 3~, type 1 Phoenix Contact VAL-CP-3S-350, AC 3~, type 2
Scope of applications Grid-connected Stand-alone Grid-connected Stand-alone Grid-connected Stand-alone
Surge protection DC, 2 strings, SunClix AC AC
Max. DC open circuit voltage 1000 V - -
Max. DC permanent voltage (L-PE) 1000 V - -
Rated voltage AC - 240 V 240 V
Max. AC permanent voltage (L-N / N-PE) - 350 / 350 V 350 / 264 V
Max. pre-fuse AC - 315 A 125 A
Rated current DC 9 A - -
Nominal lightning discharge current (8/20) s (L-N / N-PE) 10 kA 25 / 100 kA 60 / 20 kA
Max. lightning discharge current (8/20) s - - 120 / 40 kA
Lightning testing current (10/350) Ás - 100 kA -
Protection level (L-N / N-PE) < 4.48 kV < 1.5 kV < 1.4 / 1.5 kV
Response time (L-N / N-PE) < 25 ns < 100 / 100 ns < 25 / 100 ns
Cable connection (rigid / flexible) 2.5 ‑ 6 mm▓ / 2.5 ‑ 6 mm▓ 2.5 ‑ 35 mm▓ / 2.5 ‑ 25 mm▓ 2.5 ‑ 25 mm▓ / 2.5 ‑ 16 mm▓
Protection mode IP65 IP20 IP20
Dimensions (L / W / H) 112 mm / 200.0 mm / 200 mm - / 142.8 mm / ‑ - / 49.2 mm / ‑
Weight 1700 g 1748 g 416 g
Warranty 2 years 2 years 2 years
Norms IEC protection class II, EN-Type T2 IEC protection class I, EN-Type T1, IEC 61643-1 / EN 61643-11 IEC protection class II, EN-Type T2, IEC 61643-1 / EN 61643-11

Art. No. 1302162 1302163 1302164
Model Phoenix Contact VAL-CP-1S-350, AC 1~, type 2 Phoenix Contact DT-LAN-CAT.6+, Ether­net Phoenix Contact DT-TELE-RJ­45, Analogue & ISDN
Scope of applications Grid-connected Stand-alone Grid-connected Stand-alone Grid-connected Stand-alone
Surge protection AC Ethernet data circuit Analogue & ISDN data circuit
Max. DC open circuit voltage - - -
Max. DC permanent voltage (L-PE) - 3.3 V 185 V
Rated voltage AC 240 V - -
Max. AC permanent voltage (L-N / N-PE) 350 / 264 V - 130 V
Max. pre-fuse AC 125 A - -
Rated current DC - 1.5 A 0.38 A
Nominal lightning discharge current (8/20) s (L-N / N-PE) 20 / 20 kA 0.1 / 2 kA 5 / 5 kA
Max. lightning discharge current (8/20) s 40 / 40 kA - 10 kA
Lightning testing current (10/350) Ás - - -
Protection level (L-N / N-PE) < 1.4 / 1.5 kV < 0.009 / 0.7 kV < 0.25 / 0.25 kV
Response time (L-N / N-PE) < 25 / 100 ns < 1 / 100 ns < 100 / 100 ns
Cable connection (rigid / flexible) 2.5 ‑ 25 mm▓ / 2.5 ‑ 16 mm▓ RJ­45 RJ­45, 0.14 ‑ 1.5 mm▓
Protection mode IP20 IP20 IP20
Dimensions (L / W / H) - / 25.3 mm / ‑ 102 mm / 25.0 mm / 65 mm 102 mm / 25.0 mm / 65 mm
Weight 226 g 329 g 333 g
Warranty 2 years 2 years 2 years
Norms IEC protection class II, EN-Type T2, IEC 61643-1 / EN 61643-11 IEC protection class / EN-Type B2, C2, D1, IEC 61643-21 / EN 50173-1 IEC protection class / EN-Type B2, C2, C3, D1, IEC 61643-21

Art. No. 1302165
Model Phoenix Contact Plugtrab PT, sensor system
Scope of applications Grid-connected Stand-alone
Surge protection Sensor system
Max. DC open circuit voltage -
Max. DC permanent voltage (L-PE) 12.8 V
Rated voltage AC -
Max. AC permanent voltage (L-N / N-PE) 9 V
Max. pre-fuse AC -
Rated current DC 2 A
Nominal lightning discharge current (8/20) s (L-N / N-PE) 0.69 / 10 kA
Max. lightning discharge current (8/20) s 20 kA
Lightning testing current (10/350) Ás 2.5 kA
Protection level (L-N / N-PE) < 0.018 / 0.45 kV
Response time (L-N / N-PE) < 1 / 100 ns
Cable connection (rigid / flexible) 0.2 ‑ 4 mm▓ / 0.2 ‑ 2.5 mm▓
Protection mode IP20
Dimensions (L / W / H) - / 17.5 mm / ‑
Weight 653 g
Warranty 2 years
Norms IEC protection class / EN-Type C1, C2, C3, D1, IEC 61643-21